The incinerators to be supplied shall meet the following specifications
- ISO certified
 - Model: 250LA ,multiple diesel fuel combustion chambers
 - Performance capacity
 
- 120Kg/hr GRE 1.25 for HCRW
 - 96Kg/hr GRE 1.25 for general waste.
 - 40Kg/hr GRE 3.00 for plastic
 
- Waste type : health care risk waste and general waste
 - Chimney stack:
 
- Chimney : 3.5mm mild steel
 - Height from base :11m and if there are buildings within
 
30m of the incinerator, chimney must extend at least 3m
above the apexes of all the roof of such buildings
- Diameter of chimney at top :430mm
 - Weight of stack: ±500 Kg
 - Case and stack be painted with 400⁰C heat resistant Black paint
 
- Burners:
 
- 1st chamber 850⁰C – 900⁰C
 - 2nd chamber 1000⁰C
 
- Variable speed combustion air blowers
 - Primary chamber volume ±1.05 cubic metres
 - Mixing chamber volume ±0.30 cubic metres
 - Settling chamber volume ±0.89 cubic metres
 - Weight excluding chimney ±6.400Kg at manufacture
 - .Firing tools supplied :Hoe ,poker and rake
 - Dimensions
 
- Length ±2125mm
 - Width ±1890mm
 - Height ±2125mm
 - Extra width for burners ± 1000mm
 
- Loading door opening 610 *540mm
 - Hearth area ±1.19square metres
 - Description of grate/hearth :A full hearth to be supplied to prevent contaminated
 - Liquids from flowing into ash pit without being incinerated
 - Compliance with South African Atmospheric Pollution Prevention Act No.45 of
 
1965 or equivalent air pollution standards
- Documents to be supplied :Operations and maintenance manual and standard
 
operating procedures (SOPs)
- Emission controls:
 
- heated refractory screen
 - Low velocity grit settling chamber
 - Stainless steel arrester screen
 
- Refractory material :alumina content> 49% and thickness average 102mm
 - Bake out : to be done over 2-3 days
 - Materials of constructions
 
- Case :5mm mild steel
 - Bracing: heavy angle and channel
 - Hearth: 1550 ⁰C
 - Ashing door: high grade cast iron
 - Loading door 5mm mild steel lined with 1550 ⁰C castable general purpose high strength, high abrasion resistant monolithic refractory concrete.
 - Incinerator walls and roof: 1550 ⁰C castable monolithic refractory
 
- Temperature: ≥ 90 ⁰C
 - Insulation to walls: 1000 ⁰C castable insulation
 - Electricity supply required: 220volt, 15amp single phase
 - Controls:
 
- Draught control: barometer indicator, door operated draught limiter
 - Air supply: built-in forced heated air ducts, primary and secondary (intensifier)
 - Electric: control panel includes-circuit breakers, main switch, timer, pilot lights, 2 set point pyrometer and one set point pyrometer
 
Summary of Key Expected Activities/Outputs
- Replacement of pipes from the tank to the incinerator
 - Covering pipes to protect them bursting in winter
 - Replacement of gauge
 - Incinerator installation
 - Installation report
 - End of contract report